3.01 INSTALLATION

 

A.      Qualification 

    1. Cable management system and accessories to be installed by the manufacturer’s certified installation contractor to maintain the integrity of the products and acceptable performance of the completed installation.

 

B.   Inspection 

1.       Examine sub-floor for unevenness, irregularities, and dampness that would affect the quality and execution of the work. 

2.       Do not proceed with installation until subfloor surfaces are clean, dry, and clear of other trades and ready to receive cable management system. 

3.       Inspect Powerflor components for damage prior to installation. 

 

  1. Preparation and Installation

1.       The cable management system to be prepared and installed in accordance with the manufacturer’s instructions covering preparation, layout, alignment, and installation. 

2.       Sub-floor shall be level within plus or minus 0.125 inches in 10 feet, and plus or minus 0.10 inches over the entire area. System to be installed with all components loose laid over foam underlay, squarely and firmly on the sub-floor and free of rocking panels. 

3.       Provide cutouts, ramps, and closure trim as indicated and as needed.  Minimize the number of cut panels.  Layout panels to avoid less than ½ panel units.  Scribe to accurately fit trim pieces.

 

  1. Adjust and Clean

 

1.       Remove system installation debris as work progresses, maintaining area under finished system floor area in a clean condition. 

2.       The general contractor is to protect the finished floor system from damage and misuse until occupancy.

 


 